TWISTED VIDEO INTERCOM

TWISTED VIDEO INTERCOM

Eca - In accordance with European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame spread: EN 60332-1-2

Test methods :

  • CEI EN 60332-1-2:2006/A1:2016
  • CEI EN 60332-1-1:2006/A1:2016
  • EN 60332-1-2:2004/A11:2016
  • EN 60332-1-1:2004/A1:2015

Reference standards :

EN 50575 - EN 60811 - EN 50289 - EN 50290 – EN 60228 – EN 50265-2-1  -  EN 50395 – EN 50396

Cable description :

Cable used for video door entry systems, suitable for distributing power and operating signals to all BUS devices in the system. Installation must be carried out with fixed internal laying on masonry and metal structures, using passages on pipes, gangways or channels. It is not suitable for passage with underground ducts.

Conductor :

Made of annealed red copper with flexible round cord..

Core isolation :

Polyvinyl chloride (PVC) R2 quality.

Core colour :

White / Blue

Sheath :

Polyvinyl chloride (PVC) sheathing RZ quality flame retardant

Sheath colour :

Green / Brown / White / Yellow

Labeling :

Stamping on conduit every 1 m.

Technical specifications :

Insulation voltage: 400 V

Maximum operating temperature: 70° C

Minimum operating temperature: -15° C

Installation conditions :

Recommended minimum bending radius: 10 times the cable diameter

Packaging :

Hanks 100 metres – Wooden reel – Cardboard/plastic.

Conductor number

 

 

Nominal

section

mmq

Indicative diameter

mm

Indicative weight

Kg/km

Electrical resistance at 20° C.

Maximum

Ω/Km

 

 

2

0,50 4,9 20 37,7
1 6,9 45 18,9


FROR 450/750-V

FROR 450/750-V

Reference standards :

CEI 20 - 22 II - CEI 20 - 20/1 - CEI 20 – 37/2 II ed. - CEI EN 60332-1-2 - CEI EN 50267-2-1 - 2011/65/CE - 2006/95/CE - 2002/95/CE.

 Cable description :

Multicore flexible cables for dynamic applications, PVC insulated with PVC sheathing,flame retardant and low emission of corrosive gases.

 Conductor :

Annealed red copper with flexible round cord.

 Core isolation :

Polyvinyl chloride (PVC) TI2 quality.

 Core colour :

2x Brown / Blue

3G Blue/Brown / Yellow-Green

4G Brown / Black / Grey / Yellow-Green

5G Brown / Black / Grey / Blue / Yellow-Green

 Sheath :

Polyvinyl chloride (PVC) sheathing quality TM2

 Sheath colour:

Grey  RAL 7035

 Labeling :

Stamping on insulation every 1 m

Technical specifications :

Resistant to mechanical stress and chemicals.Good behaviour at low temperatures and good flexibility.

Nominal voltage: Uo/U: 450/750 V

Maximum operating temperature: 70° C

Minimum operating temperature: -15° C

Maximum short circuit temperature: : 160° C

Installation conditions :

Minimum laying temperature: 0°C

Recommended minimum bending radius: 10 times the cable diameter for mobile laying, 4 times for fixed laying.

Maximum recommended tensile stress: 15 N/mm² of copper section for mobile laying, 50 N/mm² for fixed laying.

Packaging :

Hanks 100 metres - Wooden reel

Applications :

Cables suitable for installation and mobile equipment in places with a fire hazard. The installation is foreseen inside normal or humid environments and temporarily outside. Installation in recessed and underground locations is not possible, even if protected.

Conductor number

Nominal section

 

Indicative conductor diameter

 

Average thickness Insulation Maximum outer diameter Indicative weight

 

Electrical resistance at 20° C. Massima Ω/Km
2 X 1 1,3 0,7 8,7 74 19,5
1,5 1,6 0,7 9,2 89 13,3
2,5 1,9 0,8 11,2 134 7,98
4 2,5 0,8 12,5 178 4,95
6 3 0,8 13,9 242 3,3
3 G

 

1 1,3 0,7 9,1 88 19,5
1,5 1,5 0,7 9,8 108 13,3
2,5 2 0,8 11,9 163 7,98
4 2,5 0,8 13,5 227 4,95
6 3 0,8 14,9 305 3,3
4 G

 

1 1,3 0,7 9,9 105 19,5
1,5 1,5 0,7 10,9 133 13,3
2,5 2 0,8 12,9 200 7,98
4 2,5 0,8 14,7 278 4,95
6 3 0,8 16,3 375 3,3
5 G

 

1 1,3 0,7 11,1 135 19,5
1,5 1,5 0,7 12 167 13,3
2,5 2 0,8 14,3 252 7,98
4 2,5 0,8 16,5 351 4,95
6 3 0,8 18 476 3,3


FS18OR18 300/500-V

FS18OR18 300/500-V

Cca – s3, d1, a3 -According to European Construction Products Regulation CPR R (UE) n.305/11

Reaction to fire REGULATION 305/2011/EU and standard EN 50575

Cables suitable for power supply in buildings and other civil engineering works with the aim of limiting the production and spread of fire and smoke according to the class envisaged.
Compliant with the Construction Products Regulation (CPR)

  • Standard : EN 50575:2014+A1:2016
  • Class: Cca-s3, d1, a3
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development: EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2

Reference standard :

CEI 20-40 2014/35/UE 2011/65/CE

Cable description :

FLEXIBLE cables for power, signalling and control, insulated in PVC of S18 quality, sheathed in PVC of R18 quality, with special reaction to fire characteristics and conforming to the Construction Regulation (CPR)

Conductor :

Annealed red copper with flexible round cord CLASS 5

Core isolation :

Polyvinyl chloride (PVC) quality S18

Colours :

2x Brown / Blue

3G Blue/Brown / Yellow-Green

4G Brown / Black / Grey / Yellow-Green

5G Brown / Black / Grey / Blue / Yellow-Green

Outer sheath :

Polyvinyl chloride (PVC) sheathing, R18 quality.

Colore guaina :

Brown.

Labeling :

Stamping on insulation every 1 m.

Technical specifications :

Resistant to mechanical stress, fire and flame retardant, very low emission of halogens, fumes,
toxic and corrosive gases. Good behaviour at low temperatures, good flexibility, smoothness and excellent peelability. Good resistance to abrasion.
.

Rated voltage: Uo/U 300/500 V

Maximum operating temperature: 70° C

Minimum operating temperature: -15° C

Maximum short-circuit temperature: 160° C

Laying conditions :

Minimum installation temperature: 0°C

Recommended minimum bending radius: 4 times the cable diameter

Maximum recommended tensile stress: 50 N/mm² of section

Packaging :

Hanks 100 metres - Wooden reel - Cardboard / plastic reels

Applications :

Cables for the transport of energy and transmission of signals, suitable for fixed installation in indoor areas with dry or wet environments and in areas with fire hazards. Temporary laying in outdoor areas is also permissible. For laying in free air in pipes or ducts and in metal structures.


FS17 450/750 V

FS17 450/750 V

According to European Construction Products Regulation CPR (UE) n.305/11

 Reaction to fire REGULATION 305/2011/EU and standard EN 50575 

Cables suitable for power supply in buildings and other civil engineering works with the aim of limiting the production and spread of fire and smoke.

Compliant with the Construction Products Regulation (CPR)

  • Standard : EN 50575:2014+A1:2016
  • Class: Cca-s3, d1, a3
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development: EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2

 Reference standards :

CEI UNEL 35716 - CEI EN 60332-1-2 - 2014/95/UE - 2014/35/UE - 2011/65/UE

 Cable description :

Indoor power cables and cabling, single core flexible PVC insulated cables of S17 quality, fire retardant, low corrosive gas emission and halogen free.

 Conductor :

Annealed red copper with flexible round cord CLASS 5

 Core isolation :

Polyvinyl chloride (PVC) quality S17.

 Colour :

Light blue, white, yellow/green, grey, brown, black, red, orange, pink, purple, dark blue. 

Labeling :

Stamping on insulation every 1 m.

 Technical specifications:

Resistant to mechanical stress, fire and flame retardant, very low emission of halogens, fumes,

toxic and corrosive gases. Good behaviour at low temperatures, good flexibility, smoothness and excellent peelability.

Good abrasion resistance.

Nominal voltage: Uo/U: 450/750 V

Maximum operating temperature: 70° C

Minimum operating temperature: -10° C

Maximum short circuit temperature: 160° C

 Installation conditions :

Minimum installation temperature: 5°C

Recommended minimum bending radius: 4 times the cable diameter

Maximum recommended tensile stress: 50 N/mm² of section

Packaging :

Hanks 100 metres - Wooden reel - Cardboard / plastic

Application

Single-core cables suitable for installation in exposed or concealed ducts, including in fire hazard areas, in similar closed systems and in any case only inside buildings.

Also used for fixed installation of switching and control equipment and inside luminaires.

Not suitable for outdoor installation.

Nominal

section

n° x mmq

Indicative

conductor diameter

mm

Average insulation thickness mm Maximum external diameter mm Indicative weight Kg./Km. Electrical resistance at 20° C.

Maximum  Ω/Km

1 X 1 1,3 0,7 3,2 14 19,5
1 X 1,5 1,5 0,7 3,5 19 13,3
1 X 2,5 1,9 0,8 4,2 30 7,98
1 X 4 2,5 0,8 4,8 45 4,95
1 X 6 3 0,8 6,3 63 3,3
1 X 10 3,9 1 7,6 100 1,91
1 X 16 5 1 8,8 159 1,21
1 X 25 6,2 1,2 11 255 0,78
1 X 35 7,4 1,2 12,5 345 0,554
1 X 50 8,9 1,4 14,5 490 0,386
1 X 70 10,5 1,4 17 680 0,272
1 X 95 12,2 1,6 19 895 0,206
1 X 120 13,8 1,6 21 1200 0,161
1 X 150 15,4 1,8 23,5 1400 0,129
1 X 185 16,9 2 26 1800 0,106
1 X 240 19,5 2,2 29,5 2400 0,0801


FROR 300/500-V

FROR 300/500-V

Reference standards :

CEI 20 - 22 II - CEI 20 - 20/1 - CEI 20 – 37/2 II ed. - CEI EN 60332-1-2 -CEI EN 50267-2-1 -2011/65/CE - 2006/95/CE - 2002/95/CE

Cable description :

Multicore flexible cables for dynamic applications, PVC insulated with PVC sheathing,

flame retardant and low emission of corrosive gases.

Conductor :

Annealed red copper with flexible round cord.

Core isolation :

Polyvinyl chloride (PVC) TI2 quality.

Core colour:

Black (numbered cores in white ink)

Sheath :

Polyvinyl chloride (PVC) sheathing type TM2 

Sheath colour :

Grey  RAL 7035.

Labeling :

Stamping on insulation every 1 m.

Technical specifications :

Resistant to mechanical stress and chemicals.

Good behaviour at low temperatures and good flexibility.

Nominal section: Uo/U: 300/500 V

Maximum operating temperature: 70° C

Minimum operating temperature: -15° C

Maximum short circuit temperature: 160° C

Installation conditions :

Minimum laying temperature: 0°C

Recommended minimum bending radius: 10 times the cable diameter for mobile laying, 4 times for fixed laying

Maximum recommended tensile stress: 15 N/mm² of copper section for mobile laying, 50 N/mm² for fixed laying.

Packaging :

Hanks 100 metres - Wooden reel

Application :

Cables suitable for installation and mobile equipment in places with a fire hazard.

The installation is foreseen inside normal or humid environments and temporarily outside.

Installation in recessed and underground locations is not possible, even if protected.

 

Conductor number

N

 

 

Nominal

section

 

Indicative

Conductor diameter

 

Average thickness insulation Maximum outer diameter Indicative weight

 

Electrical resistance at 20° C.

Maximum

Ω/Km

 

 

7G

1 1,3 0,6 11,1 151 19,5
1,5 1,5 0,7 13,1 215 13,3
 

10G

1 1,3 0,6 14,3 220 19,5
1,5 1,5 0,7 16,7 305 13,3
 

12G

1 1,3 0,6 14,8 250 19,5
1,5 1,5 0,7 17,5 345 13,3
 

16G

1 1,3 0,6 16,5 330 19,5
1,5 1,5 0,7 19,4 455 13,3
 

19G

1 1,3 0,6 17,7 385 19,5
1,5 1,5 0,7 20,5 520 13,3
 

24G

1 1,3 0,6 20,7 485 19,5
1,5 1,5 0,7 24,3 675 13,3
 

27G

1 1,3 0,6 21,4 600 19,5
1,5 1,5 0,7 25 720 13,3


FG16R16 - 0,6 / 1kV

FG16R16   0,6/1kV

Cca – s3, d1, a3

According to European Construction Products Regulation CPR (UE) n.305/11

Reaction to fire REGULATION 305/2011/UE

  • Standard : EN 50575:2014+A1:2016
  • Class: Cca-s3, d1, a3
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development : EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2

Reference standards:

CEI 20 – 13

CEI UNEL 35375

CEI 20 – 22 II

CEI EN 60332 -1-2

CEI EN 50267 -2-1

2014/35/UE

2011/65/CE

IEC 60502

Cable description :

Flexible energy cables insulated with rubber of G16 quality and PVC sheathing of R16 quality,

flame retardant and low emission of corrosive gases.

Conductor :

Annealed red copper with flexible round cord CLASS 5

Core isolation:

High-modulus ethylpropylene rubber G16 quality

Sheath :

Polyvinyl chloride (PVC) coating in R16 quality 

Sheath colour :

Grey  RAL 7035

Labeling :

Impression/ink stamping on sheathing depending on cross section every 1 m

Technical specifications :

Good resistance to industrial oils and greases, good behaviour at high temperatures, very low emission of fumes, toxic and corrosive gases.

Nominal voltage: Uo/U: 0.6/1 kV c.a.  –  1.500 V c.c.

Industrial test voltage: 4.000 V

Maximum operating temperature: 90° C

Minimum operating temperature: -15° C

Maximum short-circuit temperature: 250° C

 

Installation conditions

Minimum installation temperature: 0°C

Recommended minimum bending radius: 4 times the outer diameter

Maximum recommended tensile stress: 50 N/mm² of copper section

Packaging :

  • Hanks 100 metres
  • Wooden reel

Applications :

Cables used for supplying and transporting energy in residential buildings, construction sites and industry. Suitable for fixed installation both indoors and outdoors, can be buried either directly or indirectly..

Conductor number

n

Nominal

section

 

Indicative

conductor diameter

 

Average thickness insulation Approximate production

diameter

Indicative weight

Kg/km

Electrical resistance at a 20° C.

Maximum

 

 

 

 

 

 

 

 

 

 

1 x

1,5 1,5 0,7 6 50 13,3
2,5 1,9 0,7 6,3 60 7,98
4 2,5 0,7 6,9 78 4,95
6 3 0,7 7,4 98 3,3
10 4 0,7 8,4 143 1,91
16 5 0,7 9,3 197 1,21
25 6,2 0,9 11,0 295 0,780
35 7,6 0,9 12,1 385 0,554
50 8,9 1,0 13,9 525 0,386
70 10,5 1,1 15,4 715 0,272
95 12,5 1,1 17,3 935 0,206
120 13,7 1,2 18,9 1150 0,161
150 15,0 1,4 21,3 1470 0,129
185 16,9 1,6 24,5 1790 0,106
240 19,5 1,7 28,0 2290 0,0801


FG16OR16 - 0,6 / 1 kV

FG16(O)-R16    0,6 / 1 kV

Cca – s3, d1, a3

According to European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016
  • Class: Cca-s3, d1, a3
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development: EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2

Reference standards :

CEI 20 – 13

CEI UNEL 35375

CEI 20 – 22 II

CEI EN 60332 -1-2

CEI EN 50267 -2-1

2014/35/UE

2011/65/CE

IEC 60502

Cable description

Flexible energy cables insulated with rubber of G16 quality and PVC sheathing of R16 quality

flame retardant and low emission of corrosive gases.

Conductor :

Annealed red copper with flexible round cord CLASS 5

Core isolation :

High-modulus ethylpropylene rubber G16 quality

Core colour* :

2x Brown / Light blue

3x Yellow-Green / Brown / Light blue

4x Yellow-Green / Black / Grey / Brown

5x Yellow- Green / Black / Light blue / Brown / Grey

Subsequent formations with numbered cores

*Also available without G/V

Filling :

Compound of non-hygroscopic material

Sheath :

Polyvinyl chloride (PVC) coating in R16 quality

Sheath colour :

Grey  RAL 7035

Labeling :

Impression/ink stamping on sheathing depending on cross section every 1 m

Technical specifications:

Good resistance to industrial oils and greases, good behaviour at high temperatures, very low emission of fumes, toxic and corrosive gases.

Nominal voltage: Uo/U: 0.6/1 kV c.a.  –  1.500 V c.c.

Industrial test voltage: 4.000 V

Maximum operating temperature: 90° C

Minimum operating temperature: -15° C

Minimum operating temperature: 250° C

 

Installation conditions

Minimum installation temperature: 0°C

Recommended minimum bending radius: 4 times the outer diameter

Maximum recommended tensile stress: : 50 N/mm² of copper section

Packaging

  • Hanks 100 metres
  • Wooden reel

Application

Cables used for supplying and transporting energy in residential buildings, construction sites and industry. Suitable for fixed installation both indoors and outdoors, can be buried either directly or indirectly.

 

BIPOLAR
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Approximate production diameter

mm

Indicative weight Kg/km Electrical resistance at a 20° C.

Maximum

Ω/Km

2 x 1,5 1,5 0,7 9,6 127 13,3
2,5 2 0,7 10,6 168 7,98
4 2,5 0,7 11,7 215 4,95
6 3 0,7 12,7 270 3,3
10 4 0,7 14,8 390 1,91
16 5 0,7 16,6 520 1,21
25 6,2 0,9 20,8 850 0,78
35 7,4 0,9 23,0 1090 0,554
50 8,9 1 26,6 1490 0,386

 

TRIPOLAR
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Approximate production diameter

mm

Indicative weight Kg/km Electrical resistance at 20° C.

Maximum

Ω/Km

 3 G 1,5 1,5 0,7 10,1 146 13,3
2,5 2 0,7 11,2 190 7,98
4 2,5 0,7 12,3 250 4,95
6 3 0,7 13,4 320 3,3
10 4 0,7 15,7 470 1,91
16 5 0,7 17,6 695 1,21
25 6,2 0,9 22,1 1000 0,78
35 7,4 0,9 24,5 1350 0,554
50 8,9 1 28,4 1870 0,386
70 10,5 1,1 31,9 2620 0,272
95 12,2 1,1 35,4 3319 0,206
120 13,8 1,2 39,0 4130 0,161
150 15,4 1,4 43,6 5200 0,129
185 16,9 1,6 51,7 6650 0,106
240 19,5 1,7 59,0 8700 0,0801
300 23 1,8 65,4 10900 0,0641 

 

QUADRIPOLAR
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Approximate production diameter

mm

Indicative weight Kg/km Electrical resistance at 20° C.

Maximum

Ω/Km

4 G 1,5 1,5 0,7 10,8 168 13,3
2,5 2 0,7 12,0 220 7,98
4 2,5 0,7 13,3 295 4,95
6 3 0,7 14,5 385 3,3
10 4 0,7 17,0 575 1,91
16 5 0,7 19,2 795 1,21
25 6,2 0,9 24,1 1205 0,78

 

PENTAPOLAR
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Approximate production diameter

mm

Indicative weight Kg/km Electrical resistance at 20° C.

Maximum

Ω/Km

 5 G 1,5 1,5 0,7 11,7 195 13,3
2,5 2 0,7 13,0 260 7,98
4 2,5 0,7 14,5 345 4,95
6 3 0,7 15,8 455 3,3
10 4 0,7 18,6 690 1,91
16 5 0,7 21,2 970 1,21
25 6,2 0,9 26,5 1470 0,78
35 7,4 0,9 29,5 1990 0,554
50 8,9 1 34,8 3100 0,386

 

MULTIPOLAR (numbered cores)
Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Approximate production diameter

mm

Indicative weight Kg/km Electrical resistance at a 20° C.

Maximum

Ω/Km

7 G 1,5 1,5 0,7 13,4 260 13,3
7 G 2,5 2 0,7 14,9 360 7,98
10 G 1,5 1,5 0,7 16,3 390 13,4
10 G 2,5 2 0,7 18.3 525 8,06
12 G 1,5 1,5 0,7 16,8 425 13,4
12 G 2,5 2 0,7 18.9 575 8,06
16 G 1,5 1,5 0,7 18,3 500 13,4
16 G 2,5 2 0,7 20,8 700 8,06
19 G 1,5 1,5 0,7 19,3 565 13,4
19 G 2,5 2 0,7 21,8 780 8,06
24 G 1,5 1,5 0,7 22,2 730 13,5
24 G 2,5 2 0,7 25,2 995 8,1

 


FG16OM16 - 0,6 / 1kV

FG16OM16 - 0,6/1kV

Cca - s1b, d1, a1 According to European Construction Products Regulation CPR (EU) n.305/11

 Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Cca-s1b, d1, a1
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development : EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2
  • Smoke density: EN 61034-2

 Reference standards :

Construction Products Regulation (CPR).

CEI 20 - 13  -  CEI 20 - 67 - CEI UNEL 35324  - CEI EN 60332 -1-2 - 2014/35/UE - 2011/65/UE

 Cable description :

Flexible energy cables insulated with HEPR rubber of G16 quality under special thermoplastic sheathing of M16 quality

fire retardant and low emission of corrosive gases, halogen free.

 Conductor :

Annealed red copper with flexible round cord CLASS 5

 Core isolation :

High-modulus ethylpropylene rubber (HEPR) G16 quality.  

Core colour :

2x Brown / Light blue

3x Yellow-Green / Brown / Light Blue

4x Yellow-Green / Black / Grey / Brown

5x Yellow- Green / Black / Light blue / Brown / Grey

Subsequent formations with numbered cores.

*Also available without G/V

Filling :

Thermoplastic material compound LS0H (Low Smoke 0 Halogen)

Sheath :

LS0H (Low Smoke 0 Halogen) thermoplastic coating in M16 quality

Sheath colour :

Green.

Labeling :

Impression/ink stamping on sheathing depending on cross section every 1 m

Technical specifications :

Good behaviour at high temperatures, very low emission of fumes, toxic and corrosive gases, flame retardant, fire retardant and zero halogen.

Rated voltage: Uo/U: 0.6/1 kV c.a.  – 1,5  kV c.c.

Maximum operating temperature: 90° C

Minimum operating temperature: -15° C

Maximum short circuit temperature: 250° C

Installation conditions :

Minimum installation temperature: 0°C

Recommended minimum bending radius: 4 times the cable diameter

Maximum recommended tensile stress: 50 N/mm² of copper section

Packaging :

Hanks 100 metres - Wooden reel

Application :

Cables used for supplying and transporting energy in residential buildings, places with a high number of people (schools, subways, discos, theatres, shopping centres, etc.), construction sites and industry.

Suitable for installation on walls, metal structures, ducts, pipes and similar, for use indoors, even in wet rooms, and outdoors. It can also be directly and indirectly buried.

 

 

 

BIPOLAR
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/km Electrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

 

2 x

1,5 1,5 0,7 12 145 13,30
2,5 1,9 0,7 13 185 7,98
4 2,5 0,7 14,20 235 4,95
6 3 0,7 15,40 290 3,30
10 4 0,7 17,30 420 1,91
16 5 0,7 19,40 600 1,21
25 6,20 0,9 23 870 0,78
35 7,40 0,9 25,70 1135 0,554
50 8,90 1 29,30 1525 0,386

 

TRIPOLAR
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/km Electrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

 

 

 

 

 

 

3 G

1,5 1,5 0,7 12 146 13,30
2,5 2 0,7 13,50 191 7,98
4 2,5 0,7 14,90 250 4,95
6 3 0,7 16,20 320 3,30
10 4 0,7 18,20 480 1,91
16 5 0,7 20,60 705 1,21
25 6,20 0,9 24,50 1060 0,78
35 7,40 0,9 27,30 1400 0,554
50 8,90 1 31,20 1910 0,386
70 10,50 1,1 35,60 2590 0,272
95 12,20 1,1 40 3320 0,206
120 13,80 1,2 44,50 4130 0,161
150 15,40 1,4 49,50 5200 0,129
185 16,90 1,6 55,20 6650 0,106
240 19,50 1,7 61,90 8700 0,0801
300 22 1,8 68 10900 0,0641

 

QUADRIPOLAR
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/km Electrial resistance at 20° C.

Maximum

Ω/Km

 

 

 

 

4 G

1,5 1,5 0,7 13,40 168 13,30
2,5 2 0,7 14,60 220 7,98
4 2,5 0,7 16 300 4,95
6 3 0,7 17,50 390 3,30
10 4 0,7 19,80 590 1,91
16 5 0,7 22,40 865 1,21
25 6,20 0,9 26,80 1310 0,78

 

PENTAPOLAR
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/km Electrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

 

 

5 G

1,5 1,5 0,7 14,40 200 13,30
2,5 2 0,7 15,60 265 7,98
4 2,5 0,7 17,30 355 4,95
6 3 0,7 18,90 470 3,30
10 4 0,7 21,50 710 1,91
16 5 0,7 24,40 1050 1,21
25 6,20 0,9 29,30 1590 0,78
35 7,40 0,9 32,80 2110 0,554
50 8,90 1 38,20 3210 0,386

 

 

 

MULTIPOLAR (numbered cores)
Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/km Electrical resistance at 20° C.

Maximum

Ω/Km

7 G 1,5 1,5 0,7 15,40 305 13,30
7 G 2,5 2 0,7 16,80 420 7,98
10 G 1,5 1,5 0,7 18,70 395 13,40
10 G 2,5 2 0,7 20,60 525 8,06
12 G 1,5 1,5 0,7 19,30 440 13,40
12 G 2,5 2 0,7 21,30 595 8,06
16 G 1,5 1,5 0,7 21,10 545 13,40
16 G 2,5 2 0,7 23,30 750 8,06
19 G 1,5 1,5 0,7 22,10 620 13,40
19 G 2,5 2 0,7 24,50 845 8,06
24 G 1,5 1,5 0,7 25,40 765 13,50
24 G 2,5 2 0,7 28,30 1040 8,10


FG16M16 - 0,6 / 1kV

FG16M16 - 0,6 / 1kV

Cca - s1b, d1, a1 According to European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Cca-s1b, d1, a1
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development: EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2
  • Smoke density: EN 61034-2

Reference standards :

Construction Products Regulation CPR).

CEI 20 - 13  -  CEI 20 - 67 - CEI UNEL 35324  - CEI EN 60332 -1-2 - 2014/35/UE - 2011/65/UE 

Cable description :

Flexible energy cables insulated with HEPR rubber of G16 quality under special thermoplastic sheathing of M16 quality

fire retardant and low emission of corrosive gases, halogen free.

Conductor :

Annealed red copper with flexible round cord CLASS 5.

 Core isolation :

HEPR high modulus rubber in G16 quality.

Sheath :

LS0H (Low Smoke 0 Halogen) thermoplastic coating in M16 quality

Sheath colour :

Green.

Labelling :

Impression/ink stamping on sheathing

depending on cross section every 1 m

Technical specifications :

Good behaviour at high temperatures, very low emission of fumes, toxic and corrosive gases, flame retardant, fire retardant and zero halogen.

Rated voltage: Uo/U: 0.6/1 kV c.a.  – 1,5  kV c.c.

Maximum operating temperature: 90° C

Minimum operating temperature: -15° C

Maximum short circuit temperature: 250° C

Installation conditions :

Minimum installation temperature: 0°C

Recommended minimum bending radius: 4 times the cable diameter

Maximum recommended tensile stress: 50 N/mm² of copper section

Packaging :

Hanks 100 metres - Wooden reel

Applications :

Cables used for supplying and transporting energy in residential buildings, places with a high number of people (schools, subways, discos, theatres, shopping centres, etc.), construction sites and industry.

Suitable for installation on walls, metal structures, ducts, pipes and similar, for use indoors, even in wet rooms, and outdoors. It can also be directly and indirectly buried.

Conductor number

n

Nominal

Section

 

Indicative

conductor diameter

 

Average thickness Insulation Maximum outer diameter Indicative weight

Kg/km

Electrical resistance at 20° C.

Maximum

 

1 x 10 4 0,7 9,40 152 1,91
16 5 0,7 10,4 215 1,21
25 6,2 0,9 12,4 315 0,780
35 7,6 0,9 13,4 395 0,554
50 8,9 1 15,7 550 0,386
70 10,5 1,1 17,4 750 0,272
95 12,5 1,1 19 970 0,206
120 13,8 1,2 21,2 1225 0,161
150 15,4 1,4 23,8 1545 0,129
185 17,5 1,6 26 1865 0,106
240 19,5 1,7 29,2 2410 0,0801
300 22 1,8 32 2950 0,0641


H05VV-F - 300/500 V

H05VV-F - 300/500 V

 Reference standards :

CEI 20-20 /5 - CENELEC HD 21.5 S3 - CEI EN 60332-1-2 - 2011/65/CE - 2006/95/CE

Cable description :

Multicore energy cables, flexible, harmonised, with PVC insulation and sheathing

  • Non flame propagation
  • Good flexibility

Conductor :

Annealed red copper with flexible round cord CLASS 5.

 Core isolation :

Polyvinyl chloride (PVC) TI2 quality.

Core colour :

2x Brown / Blue

3x Yellow-Green / Brown / Blue

Sheath :

Polyvinyl chloride (PVC) coating TM2 quality

Sheath colour :

Black – White - Grey RAL 7035

Technical specifications : 

Rated voltage: Uo/U:  300/500 V

Maximum operating temperature: 60° C

Minimum operating temperature: -10° C

Maximum short-circuit temperature: 150° C 

Installation conditions :

Minimum installation temperature: 5°C

Recommended minimum bending radius:        

4 times the maximum outer diameter (fixed pp.)

6 times the maximum outer diameter (movable p.p.)

Maximum recommended tensile stress: 15 N/mm² of copper section 

Packaging :

Hanks 100 metres - Wooden reel

Applications :

Cables suitable for mobile laying. Suitable for installation in domestic premises, kitchens and offices as well as in humid environments. Also suitable for supplying heating and kitchen appliances as long as not in contact with hot parts and not subject to radiation. Not permitted for use in industrial agricultural buildings or outdoors and for non-domestic mechanical tools.

 

Conductor number

Nominal

section

mmq

 

Approximate

conductor diameter

mm

 

Average insulation thickness

mm

Maximum external diameter

mm

Approximate weight

Kg /km

Electrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

2 x

0,75 1,1 0,6 7,2 55 26
1 1,3 0,6 7,5 63 19,5
1,5 1,5 0,7 8,6 82 13,3
2,5 2 0,8 10,6 126 7,98
 

 

3 G

0,75 1,1 0,6 7,6 65 26
1 1,3 0,6 8,0 76 19,5
1,5 1,5 0,7 9,4 104 13,3
2,5 2 0,8 11,4 160 7,98