FS18OR18 450/750-V

FS18OR18 450/750-V

Cca – s3, d1, a3 -According to European Construction Products Regulation CPR R (UE) n.305/11

Reaction to fire REGULATION 305/2011/EU and standard EN 50575

Cables suitable for power supply in buildings and other civil engineering works with the aim of limiting the production and spread of fire and smoke according to the class envisaged.
Compliant with the Construction Products Regulation (CPR)

  • Standard : EN 50575:2014+A1:2016
  • Class: Cca-s3, d1, a3
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development: EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2

Reference standard :

CEI 20-40 2014/35/UE 2011/65/CE

Cable description :

FLEXIBLE cables for power, signalling and control, insulated in PVC of S18 quality, sheathed in PVC of R18 quality, with special reaction to fire characteristics and conforming to the Construction Regulation (CPR)

Conductor :

Annealed red copper with flexible round cord CLASS 5

Core isolation :

Polyvinyl chloride (PVC) quality S18

Colours :

2x Brown / Blue

3G Blue/Brown / Yellow-Green

4G Brown / Black / Grey / Yellow-Green

5G Brown / Black / Grey / Blue / Yellow-Green

Outer sheath :

Polyvinyl chloride (PVC) sheathing, R18 quality.

Colore guaina :

Brown.

Labeling :

Stamping on insulation every 1 m.

Technical specifications :

Resistant to mechanical stress, fire and flame retardant, very low emission of halogens, fumes,
toxic and corrosive gases. Good behaviour at low temperatures, good flexibility, smoothness and excellent peelability. Good resistance to abrasion.
.

Rated voltage: Uo/U 300/500 V

Maximum operating temperature: 70° C

Minimum operating temperature: -15° C

Maximum short-circuit temperature: 160° C

Laying conditions :

Minimum installation temperature: 0°C

Recommended minimum bending radius: 4 times the cable diameter

Maximum recommended tensile stress: 50 N/mm² of section

Packaging :

Hanks 100 metres - Wooden reel - Cardboard / plastic reels

Applications :

Cables for the transport of energy and transmission of signals, suitable for fixed installation in indoor areas with dry or wet environments and in areas with fire hazards. Temporary laying in outdoor areas is also permissible. For laying in free air in pipes or ducts and in metal structures.


H03VV-F 300/300 V

H03VV-F   300/300 V

 Reference standards :

CEI 20-20 /5 - CENELEC HD 21.5 S3 - CEI EN 60332-1-2 - 2011/65/CE - 2006/95/CE

Cable description :

Multicore energy cables, flexible, harmonised, with PVC insulation and sheathing

  • No flame propagation
  • Good flexibility

Conductor :

Annealed red copper with flexible round cord CLASS 5

Core isolation :

Polyvinyl chloride (PVC) TI2 quality

Core colour :

2x Brown / Blue

3x Yellow-Green / Brown / Blue

Sheath :

Polyvinyl chloride (PVC) coating TM2 quality.

Sheath colour :

Black - White - Grey RAL 7035

 Technical specifications : 

Rated voltage: Uo/U:  300/300 V

Maximum operating temperature: 60° C

Minimum operating temperature: -10° C

Maximum short-circuit temperature: 150° C

 Installation conditions :

Minimum installation temperature: 5°C

Recommended minimum bending radius:

4 times the maximum outer diameter (fixed p.p.)

6 times the maximum outer diameter (movable p.p.)

Maximum recommended tensile stress 15 N/mm² of copper section

 Packaging :

Hanks 100 metres - Wooden reel

Applications :

Cables suitable for mobile laying. Suitable for installation in domestic premises, kitchens and offices as well as in humid environments. Also suitable for supplying heating and kitchen appliances as long as not in contact with hot parts and not subject to radiation. Not permitted for use in industrial agricultural buildings or outdoors and for non-domestic mechanical tools.

Conductor number

Nominal

section

mmq

 

Approximate

conductor diameter

mm

 

Average insulation thickness

mm

Maximum external diameter

mm

Approximate weight

Kg /km

Electrical resistance at 20° C.

Maximum

Ω/Km

 

 

2 x

0,50 0,9 0,5 5,9 36 39
0,75 1,1 0,5 6,3 45 26
 

3 G

0,50 0,9 0,5 6,3 44 39
0,75 1,1 0,5 6,7 55 26


H03VVH2-F 300/300 V

H03VVH2-F   300/300 V

Reference standards :

CEI 20-20 /5 - CENELEC HD 21.5 S3 - CEI EN 60332-1-2 - 2011/65/CE - 2006/95/CE

Cable description :

Multicore energy cables, flexible, harmonised, with PVC insulation and sheathing

  • No flame propagation
  • Good flexibility

Conductor :

Annealed red copper with flexible round cord CLASS 5.

Core isolation :

Polyvinyl chloride (PVC) TI2 quality.

Core colour :

2x Brown/Blue

Sheath :

Polyvinyl chloride (PVC) coating TM2 quality - FLAT SHAPE.

Sheath colour :

Black - White - Grey RAL 7035

Technical specifications : 

Rated voltage: Uo/U:  300/300 V

Maximum operating temperature: 60° C

Minimum operating temperature: -10° C

Maximum short-circuit temperature: 150° C

Installation conditions :

Minimum installation temperature: 5°C

Recommended minimum bending radius:        

4 times the maximum outer diameter (fixed p.p.)

6 times the maximum outer diameter (movable p.p.)

Maximum recommended tensile stress: 15 N/mm² of copper section 

Packaging :

Hanks 100 metres - Wooden reel

Applications :

Cables suitable for mobile laying. Suitable for installation in domestic premises, kitchens and offices as well as in humid environments. Also suitable for supplying heating and kitchen appliances as long as not in contact with hot parts and not subject to radiation. Not permitted for use in industrial agricultural buildings or outdoors and for non-domestic mechanical tools.

Conductor number

Nominal

section

mmq

 

Approximate

conductor diameter

mm

 

Average insulation thickness

mm

Maximum external diameter

mm

Approximate weight

Kg /km

Electrical resistante at 20° C.

Maximum

Ω/Km

 

 

2 x

0,50 0,9 0,5 5,9 27 39
0,75 1,1 0,5 6,3 35 26
1 1,2 0,5 7 63 19,5

 

 

 

 


FFROR 300/500 V - 450/750 V

FFROR 300/500 V  -  450/750 V

 

Reference standards :

CEI 20 – 20/5  - CEI 20 – 11  - CEI 20 - 29

 

Cable description :

Extremely flexible cables for use in office equipment or domestic applications as extension cables for large appliances, mobile appliances and uses subject to frequent movement.

 

Conductor :

Red copper flexible round cord CLASS 6.

 

Core isolation :

Polyvinyl chloride (PVC) compound TI2.

 

Core colour :

2x Brown / Blue

3G Blue / Brown / Yellow-Green

4G Brown/Black/Grey/Yellow-Green

 

Sheath :

Polyvinyl chloride (PVC) based compound quality TM2.

 

Sheath colour :

Orange

 

Technical specifications :

Extreme flexibility.

Rated voltage: Uo/U: 300/500 V (for 1 mmq conductors) - 450/750 V (for 1.5/2.5 mmq conductors)

Maximum operating temperature: 70° C

Minimum operating temperature: -10° C

Maximum short circuit temperature: 160° C

 

Installation conditions :

Minimum laying temperature: 0°C

Recommended minimum bending radius:

10 times the cable diameter for mobile laying, 4 times for fixed laying.

Maximum recommended tensile stress:

50 N/mm² total section of the copper for fixed laying.

 

Packaging :

Hanks 100 metres - Wooden reel.

 

Applications :

Extremely flexible cables for portable devices, household appliances, tool extensions.

Conductor number

Nominal

section

mmq

 

Approximate

conductor diameter

mm

 

Average insulation thickness

mm

Maximum external diameter

mm

Approximate weight

Kg /km

Electrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

2 x

11,30,78,88019,5
1,51,50,79,39213,3
2,51,90,8111457,98
 

 

3 G

11,30,79,49519,5
1,51,50,79,811513,3
2,51,90,8121657,98
 

 

4 G

11,30,71011519,5
1,51,50,71114013,3
2,51,90,8132057,98


H01N2-D 100/100 V

H01N2-D  -   100/100 V

Reference standards

CEI 20-19 /6

HD 22.6

CEI EN 60332-1-2

2006/95/CE

2011/65/CE

Cable description

Harmonised rubber-sheathed super-flexible single-core power transmission cables for arc welding machines.

Conductor

Red copper flexible round cord CLASS 5

 

Colour

Black

 

Insulation

Gomma

 

Labeling

Stamping every 1m

 

Technical specifications

Resistant to oil, mechanical stress and abrasion, fire and flame retardant, resistant to continuous bending and twisting.

Very good flexibility and UV resistance

 

Rated voltage: Uo/U: 100/100 V

Maximum operating temperature: 85° C

Minimum operating temperature: -35° C

Maximum short circuit temperature: 250° C

 

Installation conditions

Minimum laying temperature: (mobile laying) -25°C a 85 °C

Recommended minimum bending radius: 6 times the cable diameter

Maximum recommended tensile stress: 50 N/mm² of section

 

Packaging

  • Hanks 100 metres
  • Wooden reel

Applications

Single-core cables suitable for mobile connections for the transmission of high currents from the electric welding device to the welding tool itself, thanks to their extreme resistance to movement and their excellent flexibility.

 

Nominal

section

N°x mmq

Indicative

conductor diameter

 

Average thickness Insulation Maximum outer diameter Approximate weight

Kg/Km

Electrical resistance at 20° C.

Maximum

Ω/Km

 

1 x 10 3,9 2 10 175 1,91
1 x 16 5 2 10 220 1,21
1 x 25 6,6 2 13 310 0,78
1 x 35 7,7 2 14 415 0,554
1 x 50 9,4 2 17 560 0,386
1 x 70 11 2,4 19 780 0,272
1 x 95 12,5 2,6 21 1030 0,206
1 x 120 15,5 2,8 24 1305 0,161
1 x 150 15,5 3 26 1600 0,129


H07RN- F - 450/750 V

H07RN- F - 450/750 V

Eca

According to European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame spread: EN 60332-1-2

 

Reference standards

CEI EN 60332-1

CEI EN 50255-2-21

CEI 20-19/4  HD 22.4 S4

CEI 20-107/2-21

2006/95/CE

2011/65/CE 

Cable description

Harmonised flame retardant rubber insulated polychloroprene (neoprene) sheathed cables

with high resistance to water, mineral oils, industrial greases and average mechanical stress,

with good flexibility and good resistance to ozone and chemicals.

Conductor

Flexible bare copper CLASS 5

Insulation

Special elastomeric (rubber) EI4 quality

Core colour

2x Brown / Light Blue

3x Yellow-Green / Brown / Light Blue

4x Yellow-Green / Black / Grey / Brown

5x Yellow-Green / Black / Light Blue / Brown / Grey

Subsequent formations with numbered cores

*Also available without G/V

Sheath

Polychloroprene (Neoprene) with high mechanical properties

Sheath colour

Black

Labeling

White ink stamping on the conduit every 1 m

Technical specifications

Rated voltage: Uo/U: 450/750 V c.a. - 0.6 /1 kV c.c.

Maximum operating temperature: 60° C

Minimum operating temperature: -40° C (in assenza di sollecitazioni meccaniche)

Maximum short circuit temperature: 200° C

 

Installation conditions 

Recommended minimum bending radius:

6 times the outside diameter of the cable for mobile laying

3 times the outside diameter of the cable for fixed laying (if < or = 12mm)

4 times the external diameter of the cable for fixed laying (if  >  12mm)

Maximum recommended tensile stress:

15 N/mm2 section for mobile laying

50 N/mm2 of section for fixed laying

Packaging

  • Hanks 100 metres
  • Wooden reel

 

Applications

Cables suitable for installation in dry, damp, wet and open areas, and in workshops with explosive atmospheres.

For supplying and connecting mobile and lifting equipment and/or similar systems.

Recommended for connections subject to medium mechanical stress: agricultural and industrial workshop equipment,

heating plates, large kettles, portable lamps, power tools such as drills, motors or transportable machines on construction sites or in agricultural applications. They can also be used in temporary

buildings or construction site huts.

Use is permitted up to 1,000 V AC in the case of protected fixed installation in pipes.

Mechanical protection is required when used in indirect underground installation (installation criteria for flexible cables).

 

UNIPOLAR
Conductor number

n

Nominal

Section

 

Indicative

conductor diameter

 

Average thickness Insulation Maximum outer diameter Indicative weight

Kg/km

Electrical resistance at 20° C.

Maximum

 

 

 

 

 

 

 

 

 

 

1 x

1,51,50,87,15113,3
2,520,97,9677,98
42,519924,95
6319,81213,3
1041,211,91861,91
1651,213,42561,21
255,91,415,83680,780
357,31,417,94850,554
508,91,620,66680,386
7010,51,623,39050,272
9512,201,82611800,206
12013,801,828,614600,161
15015,40231,418100,129
18516,92,234,421650,106
24019,52,438,327500,0801 

 

BIPOLARI
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/kmElectrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

 

2 x

11,30,8109319,50
1,51,50,81111513,30
2,51,90,913,101657,98
42,5115,202254,95
63116,803003,30
1041,222,605501,91
1651,225,707401,21
256,21,430,7010600,78

 

TRIPOLARI
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/kmElectrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

 

 

 

 

 

 

3 G

11,300,810,7012019,5
1,51,500,81215013,30
2,520,913,502007,98
42,50114,902954,95
63116,203803,30
1041,218,206751,91
1651,220,609501,21
256,201,424,5013550,78
357,401,427,3017650,554
508,901,631,2024150,386
7010,501,635,6032300,272
9512,201,84042250,206
12013,801,844,5051900,161
15015,40249,5064150,129
18516,502,255,2077000,106

 

QUADRIPOLARI
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/kmElectrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

 

4 G

11,30,811,914519,5
1,51,50,813,117513,3
2,520,915,52557,98
42,5117,93554,95
631204853,30
1041,226,58451,91
1651,230,111851,21
256,201,436,617300,78 

 

PENTAPOLARI
Conductor

number

n

Nominal

section

mmq

Approximate

conductor diameter

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/kmElectrical resistance at 20° C.

Maximum

Ω/Km

 

 

 

 

5 G

11,30,813,118019,5
1,51,50,814,422013,30
2,520,9173107,98
42,5119,94454,95
63122,26053,30
1041,229,110351,91
1651,233,314651,21
256,201,440,421450,78 

 

MULTIPOLARI (anime numerate)
Nominal

section

mmq

Approximate

conductor section

mm

Average insulation

thickness

mm

Maximum external diameter

mm

Indicative weight Kg/kmElectrical resistance at 20° C.

Maximum

Ω/Km

7G1,51,50,817,235513,3
7G2,520,9204957,98
12G1,51,50,822,450513,3
12G2,520,926,27107,98
19G1,51,50,826,372513,3
19G2,520,930,910357,98
24G1,51,50,830,791513,3
24G2,520,936,413257,98

 


FLEX INTERCOM NPI

FLEX INTERCOM NPI

Eca - According to European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame spread: EN 60332-1-2

 Test methods :

  • CEI EN 60332-1-2:2006/A1:2016
  • CEI EN 60332-1-1:2006/A1:2016
  • EN 60332-1-2:2004/A11:2016
  • EN 60332-1-1:2004/A1:2015

Reference standards :

CEI 20-22 - CEI 79-1 - IEC 332-15

Cable description :

Fire retardant signalling and control cables, with outer jacket and PVC compound inner insulation.

Cable suitable for intercom, electronics and computer systems.

Conductor :

Annealed red copper with flexible round cord.

Core isolation :

Polyvinyl chloride (PVC) TI2 quality.

Core colour :

Brown / Blue / Yellow / Green / Black / Grey / Orange / Pink

Red / White / Purple / Light Green / Light Yellow / Light Brown / Light Blue

Sheath :

Polyvinyl chloride (PVC) sheathing quality TM2.

Sheath colour :

Grey  RAL 7035

Labeling :

Stamping on insulation every 1m.

Technical specifications :

Rated voltage: Uo/U: 300/300 V

Test voltage: 1500 V

Maximum operating temperature: 70° C

Minimum operating temperature: -10° C

Installation conditions :

Recommended minimum bending radius: 15 times the cable diameter

Packaging :

Hanks 100 metres - Wooden reel

Conductor number

 

 

Nominal

section

mmq

Approximate

conductor diameter

mm

 

Average insulation thickness

mm

Maximum external diameter

mm

Indicative weight

Kg/km

Electrical resistance at a 20° C.

Maximum

Ω/Km

 

2 0,50 1,85 0,5 4,5 31 39
4 0,50 1,85 0,5 5,3 48 39
6 0,50 1,85 0,5 6,3 70 39
8 0,50 1,85 0,5 7,5 88 39
10 0,50 1,85 0,5 8,2 121 39
12 0,50 1,85 0,5 8,5 127 39
14 0,50 1,85 0,5 8,9 146 39


250/250 V FLEX PERMUTATOR

250/250 V FLEX PERMUTATOR

References standard :

CEI 20-11 - CEI 20-35 - CEI 20-22 II - CEI 46-5

Cable description :

Cables for plant connections with internal conductors insulated with PVC compound. Used wherever it is necessary to connect civil and industrial machines and systems.

Conductor :

Annealed red copper with flexible round cord.

Core isolation :

Polyvinyl chloride (PVC) TI2 quality.

Core colour :

Brown / Blue / Yellow / Green / Black / Grey / Orange / Pink

Red / White / Purple / Light Green / Light Yellow / Light Brown / Light Blue

Sheath :

Unsheathed cable.

Technical specifications :

Rated voltage: Uo/U: 250/250 V

Test voltage: 1500 V

Maximum operating temperature: 70° C

Minimum operating temperature: -10° C

Installation conditions :

Recommended minimum bending radius: 15 times the cable diameter.

Packaging :

Hanks 100 metres - Wooden reel

Conductor number

 

 

Nominal

section

mmq

Approximate

conductor diameter

mm

 

Average insulation thickness

mm

Maximum external diameter

mm

Indicative weight

Kg/km

Electrical resistance at a 20° C.

Maximum

Ω/Km

 

2 0,50 1,85 0,5 4,5 31 39
4 0,50 1,85 0,5 5,3 48 39
5 0,50 1,85 0,5 5,8 60 39
6 0,50 1,85 0,5 6,3 70 39
7 0,50 1,85 0,5 6,9 79 39
8 0,50 1,85 0,5 7,5 88 39
10 0,50 1,85 0,5 8,2 121 39
12 0,50 1,85 0,5 8,5 127 39
14 0,50 1,85 0,5 8,9 146 39


DOUBLE TELEPHONE SWITCH

DOUBLE TELEPHONE SWITCH

Reference standards :

CEI 20-20

Cable description :

Cables for telephone equipment connections, transmission and patching in telephone exchanges.

Conductor :

Made of annealed red copper with rigid round cord - approximate conductor diameter 0.60 mm.

Core isolation :

Polyvinyl chloride (PVC).

Core colour :

Red / White

Sheath :

Unsheathed cable.

Technical specifications :

Nominal cross-section: 2 x 0,30 mmq

Test voltage: 1000 V c.a.

Maximum operating temperature : 80° C

Minimum operating temperature: -10° C

Installation conditions :

Fixed

Packaging :

Coils 100 / 250 / 500 metres - Cardboard / plastic reels


ALARM CABLE

ALARM CABLE

Eca In accordance with the European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/UE :

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame spread: EN 60332-1-2

Test methods :

  • CEI EN 60332-1-2:2006/A1:2016
  • CEI EN 60332-1-1:2006/A1:2016
  • EN 60332-1-2:2004/A11:2016
  • EN 60332-1-1:2004/A1:2015

Reference standards :

CEI 20-29 IEC 60228 - CEI 20-11 - CEI 20-35 IEC 60332.1 - CEI 20-22 II IEC 60332.3 - CEI 20/37 IEC 61034-2 - CEI UNEL 36762

Cable description :

Shielded cables suitable for connecting alarm and burglar alarm systems in residential and public areas.


The shielding is necessary due to the signal being transmitted at very low frequencies.

Conductor :

Flexible copper CLASS 5, concentric layers stranded.

Core isolation :

Polyvinyl chloride (PVC) R2 quality.

Core colour :

Brown / Blue / Yellow / Green / Black / Grey / Orange / Pink

Red / White / Purple / Light Green / Light Yellow / Light Brown / Light Blue

Shield :

100% coverage. Aluminium/polyester tape overlaid with flexible red copper continuity conductor

Sheath :

Polyvinyl chloride (PVC) sheathing RZ quality flame retardant

Colour sheath :

White / Grey RAL 7035

Labeling :

Stamping on conduit every 1m.

Technical specifications :

Operating voltage : 300/500 V

Test voltage: 4000 V c.c.

Maximum operating temperature: 70° C

Minimum operating temperature: -10° C

Installation conditions :

Recommended minimum bending radius: 10 times the cable diameter

 

Packaging :

Hanks 100 metres - Wooden Reel - Cardboard/plastic reels

Conductor

number

n

Nominal

section

mmq

Aproximate conductor

diametere

mm

Average insulation

thickness

mm

Maximum external diameter

Mm

Indicative weight Kg/km Electrical resistance at a 20° C.

Maximum

Ω/Km

 

2x 0,22+T 0,22 0,7 0,4 3,6 18 0,22 – 90
4x 0,22+T 0,22 0,7 0,4 4,2 27 0,22 – 90
6x 0,22+T 0,22 0,7 0,4 5 38 0,22 – 90
8X 0,22+T 0,22 0,7 0,4 5,5 44 0,22 – 90
2X 0,22+ 2X 0,50+T 0,50 0,9 0,5 5 38 0,50 - 39
4X 0,22+ 2X 0,50+T 0,50 0,9 0,5 5,5 44 0,50 – 39
6X 0,22+ 2X 0,50+T 0,50 0,9 0,5 5,8 52 0,50 – 39
8X 0,22+ 2X 0,50+T 0,50 0,9 0,5 6,2 56 0,50 – 39
10X 0,22+ 2X 0,50+T 0,50 0,9 0,5 6,6 61 0,50 - 39
2X 0,22+ 2X 0,75+T 0,75 1,1 0,5 5,5 45 0,75 - 26
4X 0,22+ 2X 0,75+T 0,75 1,1 0,5 5,8 49 0,75 – 26
6X 0,22+ 2X 0,75+T 0,75 1,1 0,5 6 52 0,75 – 26
8X 0,22+ 2X 0,75+T 0,75 1,1 0,5 6,5 62 0,75 – 26
10X 0,22+ 2X 0,75+T 0,75 1,1 0,5 6,8 65 0,75 – 26