24V VDC AUTOMATION

24V VDC AUTOMATION

Eca In accordance with the European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EUE

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Verticla flame spread: EN 60332-1-2 

Test methods :

  • CEI EN 60332-1-2:2006/A1:2016
  • CEI EN 60332-1-1:2006/A1:2016
  • EN 60332-1-2:2004/A11:2016
  • EN 60332-1-1:2004/A1:2015

Reference standards :

CEI 20-29 IEC 60228 - CEI 20-11- CEI 20-35 IEC 60332.1 - CEI 20-22 II IEC 60332.3 - CEI 20/37 IEC 61034-2 - CEI UNEL 36762

Cable description :

Fire retardant double sheathed cables for automation systems, which are installed to connect control and signalling equipment and where it is necessary to transmit signals without interference.
control and signalling equipment and where it is necessary to transmit signals that are not affected by electromagnetic interference. electromagnetic interference.

In addition, protection against UV and external interference agents is ensured by the chemical composition of the sheaths.

Conductor :

Annealed red copper with flexible round cord

Core isolation:

Polyvinyl chloride (PVC) R2 quality

Core colour Anime :

Red / Black / Brown / Blue / Grey / Yellow-green

Core colour :

Rivestimento in guaina polivinilcloruro (PVC) qualità RZ antifiamma.

Primary sheath :

White

Secondary sheath :

Polyvinyl chloride (PVC) sheathing RZ quality flame retardant

Colour Secondary sheath :

Green / Purple / Blue / Grey / Yellow

Labeling :

Stamping on conduit every 1m

Technical specifications :

Rated voltage: Uo/U: 100/100 V

Test voltage:  4000 V

Maximum operating temperature: 70° C

Minimum operating temperature: -10° C

Installation conditions :

Recommended minimum bending radius: 10 times the cable diameter

Packaging :

Hanks 100 metres - Wooden reel

Conductor number

N

 

 

Nominal

Section

mmq

External diameter

mm

Peso indicativo

Kg/km

Electrical resistance at 20° C.

Maximum

Ω/Km

 

2 0,50 5,4 40 37,7
2 1 6,8 65 18,9
2 1,5 7,8 86 13,2
4 0,50 6,2 57 37,7
4 1 7,9 96 18,9
4 1,5 9 126 13,2
6 0,50 7,4 82 37,7
6 1 9,4 139 18,9
6 1,5 10,6 181 13,2


FIRE RESISTANT

FIRE RESISTANT

Reference standards :

UNI 9795 EN 50200/CEI/36-4-0 - CEI 20-29 EN 60228 CL.C - CEI EN 50363-0 - CEI EN 60332-1-2 - CEI EN 61034

20/37 IEC 61034-2 - CEI EN 50200 CEI 20/36-4-0 - CEI 20-105 UNI 9795

Cable description :

Cable for power supply, control and signalling to enable operation of safety systems in the event of fire

Conductor :

Red copper round flexible cord CLASS 5

Core isolation :

LSZH (elastomeric) compound quality G10

Shielding :

Cover 100% Aluminium/Polyester tape topped with flexible or rigid continuity conductor (red/tinned copper)

Sheath :

M1-quality LSZH compound (halogen free)

Sheath Color :

Red RAL 3000

Labeling :

Stamping on conduit every 1m.

Technical Specifications :

Fire resistance 30 min a 830 °C

Fire resistance 90 min a 830 °C

Fire resistance 120 min a 830 °C

Fire resistance 180 min a 750 °C

Operating voltage: 450/750 V

Maximum operating temperature: 90° C

Minimum operating temperature: -40° C

Short-circuit temperature: 350 °C

* Fire resistance grade to be specified

Installation conditions :

Recommended minimum bending radius: 8 times the cable diameter.

Applications :

Cable used for safety installations and circuits in hospitals, cinemas, fire pumps, public places where fire resistance of the cables used is required and the cable is able to withstand the high temperatures released in the event of fire.
For fixed indoor and outdoor installation. Can be installed on pipes, ducts, cable trays and similar systems.
Indirect underground laying allowed.

Packaging :

Hanks 100 metres – Wooden reel / Cardboard/plastic reels

Nominal

Section

mmq

Electrical resistance at 20° C.

<Maximum

Ω/Km

0,50 42
1 19
1,5 13,3
2,5 8


LAN CABLE - UTP / FTP

CAVO LAN AWG 24 CAT.5E / CAT.6E

  • UTP (unshielded)
  • FTP (shielded)

Eca
In accordance with the European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame spread: EN 60332-1-2

Test methods :

  • CEI EN 60332-1-2:2006/A1:2016
  • CEI EN 60332-1-1:2006/A1:2016
  • EN 60332-1-2:2004/A11:2016
  • EN 60332-1-1:2004/A1:2015

Reference standards :

CEI 20/29 IEC 60228 - CEI 20-11 - CEI 20-35 IEC 60332.1 - CEI 20-22 II IEC 60332.3 - CEI 20/37 IEC 61034-2

Cable description :

Cables used for voice and data transmission between exchanges and peripherals in structured cabling systems in buildings. Flame retardant.

Conductor :

Coppie riunite tra loro avvolte da nastro in poliestere in rame/alluminio.

Insulation :

Polyethylene compound

Shielding by FTP type :

Matched pairs wrapped with polyester copper/aluminium tape

Sheath :

Flame resistant polyvinyl chloride (PVC) sheathing type RZ

Color sheath :

White / Grey / Black

Labeling :

Stamping on insulation every 1m

Technical specifications :

Operating voltage:  300/500 V

Test voltage : 1500 V

Operating temperature : -10  / +70 °Cù

Maximum loop resistance at 20°C : 16,8 OHM/km

Maximum mutual capacitance at 1 KHz : 49 nF/Km

Bending radius :  25 (UTP) / 28 (FTP)

Packaging :

Hanks 100 metres - Cardboard boxes 305 metres - Cardboard/plastic/wood reels


COAXIAL CABLE - MINI SAT

COAXIAL CABLE - MINI SAT

Eca In accordance with the European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame spread: EN 60332-1-2

 Test methods :

  • CEI EN 60332-1-2:2006/A1:2016
  • CEI EN 60332-1-1:2006/A1:2016
  • EN 60332-1-2:2004/A11:2016
  • EN 60332-1-1:2004/A1:2015

Reference standards :

CEI EN 60332-1-2:2006/A1:2016
CEI EN 60332-1-1:2006/A1:2016
EN 60332-1-2:2004/A11:2016
EN 60332-1-1:2004/A1:2015

Cable description :

Cables used for TV aerials, audio and video reception and data transmission

Conductor :

Copper/aluminium Rigid 0.51 mm/0.58 mm

Dielectric : PEE

Shield :

Tape screen: 100 % aluminium/polyester

Screen Braid: CU/SN 65 %

Sheath :

Polyvinyl chloride (PVC) sheathing

Colour sheath:

White

Labeling :

Stamping on insulation every 1m.

Technical specifications:

Characteristic impedance : 75 ± 3 Ohm

Mutual capacitance : 55 pF/m

Relative propagation speed : 80 %

Packaging :

Hanks 100 metres - Cardboard/plastic reels


COMPOSITE COAX + POWER SUPPLY

COMPOSITE COAX + POWER SUPPLY

Eca - In accordo alla normativa Europea Prodotti da Costruzione CPR (UE) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standad : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame spread: EN 60332-1-2 

Test methods :

  • CEI EN 60332-1-2:2006/A1:2016
  • CEI EN 60332-1-1:2006/A1:2016
  • EN 60332-1-2:2004/A11:2016
  • EN 60332-1-1:2004/A1:2015

Reference standards :

CEI 20/29 IEC 60228 - CEI 20-11 - CEI 20-35 IEC 60332.1 - CEI 20-22 II IEC 60332.3 - CEI 20/37 IEC 61034-2 - CEI UNEL 36762

Cable description

Cables used in video intercom systems where video and control signals are transmitted via a twisted pair and video surveillance to connect the camera to the DVR with a single cable

Conductor :

2 flexible class 5 red copper conductors

1 coaxial rigid copper conductor

Insulation :

PVC compound type R2

Shielding :

Aluminium/polyester tape topped with flexible red copper continuity conductor (100%)

Sheath :

Flame resistant polyvinyl chloride (PVC) sheathing type RZ

Stealth colour :

White / Grey

Labeling :

Stamping on conduit every 1m

Technical specifications :

Operating temperature: -10 / +70 °C

Packaging :

Hanks 100 metres - Cardboard / plastic reels


PIATTINA HI-FI / COSTA STRETTA

HI-FI RIBBON / NARROW RIB

According to European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame speed: EN 60332-1-2

Test methods :

  • CEI EN 60332-1-2:2006/A1:2016
  • CEI EN 60332-1-1:2006/A1:2016
  • EN 60332-1-2:2004/A11:2016
  • EN 60332-1-1:2004/A1:2015

Reference standards :

CEI 20-22 - CEI 79-1 - IEC 332-1

Cable description :

Bipolar cables for audio transmission, hi-fi, powering table lamps or light portable appliances.

Conductor :

Flexible bare copper

Insulation :

Polyvinyl chloride (PVC) flame retardant quality

Insulation colours :

  • Red-Black
  • Polarized
  • White
  • Black
  • Grey
  • Brown
  • Silver
  • Gold
  • Bronze

Technical specifications :

Test voltage : 1500 V

Insulation resistance: min. 200 M Ω/Km

Operating temperature : 5 °C / 70°C

Packaging :

Hanks 100 metres - Wooden reel - Cardboard / plastic reel


COPPER CORD

COPPER CORD

STANDARD CEI UNEL 01437 p.q.a.

Supply status:

  • FTE
  • CRUDE
  • RICE
  • RED / TINNED

Reference standards :

CEI UNEL 01437 p.q.a.

Description :

Used to connect earth installations, where the route should be as short as possible.
The rope must not be subjected to mechanical stress and must not be susceptible to corrosion and mechanical wear.
Use for overhead power lines is not permitted.

Technical specifications :

Maximum tensile stress : 5 kg/mmq.

Recommended minimum bending :

6 times the outside diameter.

Packaging :

Hanks 100 metres - Wooden reel

NOMINAL

SECTION

MMq

FORMATION

No OF

wires x 0MM

THEORETICAL

SECTION

MMq

ROPE

DIAMETER

 MM

APPROX

WEIGHT.

Kg/Km

BROKEN

LOAD. MIN.

Kg

RESISTIVITY

20° C.

Ω/Km

 

10 7 x 1,35 10 4,05 90,9 399 1,810
16 7 x 1,70 15,9 5,10 144 634 1,140
25 7 x 2,14 25,2 6,42 228 981 0,720
35 7 x 2,52 34,9 7,56 316 1359 0,520
50 7 x 3,0 49,5 9 449 1928 0,366
70 19 x 2,14 68,8 10,70 626 2623 0,263
95 19 x 2,52 94,8 12,60 867 3615 0,191