FS17 450/750 V

According to European Construction Products Regulation CPR (UE) n.305/11

 Reaction to fire REGULATION 305/2011/EU and standard EN 50575 

Cables suitable for power supply in buildings and other civil engineering works with the aim of limiting the production and spread of fire and smoke.

Compliant with the Construction Products Regulation (CPR)

  • Standard : EN 50575:2014+A1:2016
  • Class: Cca-s3, d1, a3
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development: EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2

 Reference standards :

CEI UNEL 35716 - CEI EN 60332-1-2 - 2014/95/UE - 2014/35/UE - 2011/65/UE

 Cable description :

Indoor power cables and cabling, single core flexible PVC insulated cables of S17 quality, fire retardant, low corrosive gas emission and halogen free.

 Conductor :

Annealed red copper with flexible round cord CLASS 5

 Core isolation :

Polyvinyl chloride (PVC) quality S17.

 Colour :

Light blue, white, yellow/green, grey, brown, black, red, orange, pink, purple, dark blue. 

Labeling :

Stamping on insulation every 1 m.

 Technical specifications:

Resistant to mechanical stress, fire and flame retardant, very low emission of halogens, fumes,

toxic and corrosive gases. Good behaviour at low temperatures, good flexibility, smoothness and excellent peelability.

Good abrasion resistance.

Nominal voltage: Uo/U: 450/750 V

Maximum operating temperature: 70° C

Minimum operating temperature: -10° C

Maximum short circuit temperature: 160° C

 Installation conditions :

Minimum installation temperature: 5°C

Recommended minimum bending radius: 4 times the cable diameter

Maximum recommended tensile stress: 50 N/mm² of section

Packaging :

Hanks 100 metres - Wooden reel - Cardboard / plastic

Application

Single-core cables suitable for installation in exposed or concealed ducts, including in fire hazard areas, in similar closed systems and in any case only inside buildings.

Also used for fixed installation of switching and control equipment and inside luminaires.

Not suitable for outdoor installation.

Nominal

section

n° x mmq

Indicative

conductor diameter

mm

Average insulation thickness mm Maximum external diameter mm Indicative weight Kg./Km. Electrical resistance at 20° C.

Maximum  Ω/Km

1 X 1 1,3 0,7 3,2 14 19,5
1 X 1,5 1,5 0,7 3,5 19 13,3
1 X 2,5 1,9 0,8 4,2 30 7,98
1 X 4 2,5 0,8 4,8 45 4,95
1 X 6 3 0,8 6,3 63 3,3
1 X 10 3,9 1 7,6 100 1,91
1 X 16 5 1 8,8 159 1,21
1 X 25 6,2 1,2 11 255 0,78
1 X 35 7,4 1,2 12,5 345 0,554
1 X 50 8,9 1,4 14,5 490 0,386
1 X 70 10,5 1,4 17 680 0,272
1 X 95 12,2 1,6 19 895 0,206
1 X 120 13,8 1,6 21 1200 0,161
1 X 150 15,4 1,8 23,5 1400 0,129
1 X 185 16,9 2 26 1800 0,106
1 X 240 19,5 2,2 29,5 2400 0,0801