FG16OM16 - 0,6/1kV
Cca - s1b, d1, a1 According to European Construction Products Regulation CPR (EU) n.305/11
Reaction to fire REGULATION 305/2011/EU
- Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
- Class: Cca-s1b, d1, a1
- Classification (CEI UNEL 35016): EN 13501-6
- Heat and smoke emission during flame development : EN 50399
- Vertical flame spread: EN 60332-1-2
- Corrosive and halogenated gases: EN 60754-2
- Smoke density: EN 61034-2
Reference standards :
Construction Products Regulation (CPR).
CEI 20 - 13 - CEI 20 - 67 - CEI UNEL 35324 - CEI EN 60332 -1-2 - 2014/35/UE - 2011/65/UE
Cable description :
Flexible energy cables insulated with HEPR rubber of G16 quality under special thermoplastic sheathing of M16 quality
fire retardant and low emission of corrosive gases, halogen free.
Conductor :
Annealed red copper with flexible round cord CLASS 5
Core isolation :
High-modulus ethylpropylene rubber (HEPR) G16 quality.
Core colour :
2x Brown / Light blue
3x Yellow-Green / Brown / Light Blue
4x Yellow-Green / Black / Grey / Brown
5x Yellow- Green / Black / Light blue / Brown / Grey
Subsequent formations with numbered cores.
*Also available without G/V
Filling :
Thermoplastic material compound LS0H (Low Smoke 0 Halogen)
Sheath :
LS0H (Low Smoke 0 Halogen) thermoplastic coating in M16 quality
Sheath colour :
Green.
Labeling :
Impression/ink stamping on sheathing depending on cross section every 1 m
Technical specifications :
Good behaviour at high temperatures, very low emission of fumes, toxic and corrosive gases, flame retardant, fire retardant and zero halogen.
Rated voltage: Uo/U: 0.6/1 kV c.a. – 1,5 kV c.c.
Maximum operating temperature: 90° C
Minimum operating temperature: -15° C
Maximum short circuit temperature: 250° C
Installation conditions :
Minimum installation temperature: 0°C
Recommended minimum bending radius: 4 times the cable diameter
Maximum recommended tensile stress: 50 N/mm² of copper section
Packaging :
Hanks 100 metres - Wooden reel
Application :
Cables used for supplying and transporting energy in residential buildings, places with a high number of people (schools, subways, discos, theatres, shopping centres, etc.), construction sites and industry.
Suitable for installation on walls, metal structures, ducts, pipes and similar, for use indoors, even in wet rooms, and outdoors. It can also be directly and indirectly buried.
BIPOLAR | ||||||
Conductor
number n |
Nominal
section mmq |
Approximate
conductor diameter mm |
Average insulation
thickness mm |
Maximum external diameter
mm |
Indicative weight Kg/km | Electrical resistance at 20° C.
Maximum Ω/Km |
2 x |
1,5 | 1,5 | 0,7 | 12 | 145 | 13,30 |
2,5 | 1,9 | 0,7 | 13 | 185 | 7,98 | |
4 | 2,5 | 0,7 | 14,20 | 235 | 4,95 | |
6 | 3 | 0,7 | 15,40 | 290 | 3,30 | |
10 | 4 | 0,7 | 17,30 | 420 | 1,91 | |
16 | 5 | 0,7 | 19,40 | 600 | 1,21 | |
25 | 6,20 | 0,9 | 23 | 870 | 0,78 | |
35 | 7,40 | 0,9 | 25,70 | 1135 | 0,554 | |
50 | 8,90 | 1 | 29,30 | 1525 | 0,386 |
TRIPOLAR | ||||||
Conductor
number n |
Nominal
section mmq |
Approximate
conductor diameter mm |
Average insulation
thickness mm |
Maximum external diameter
mm |
Indicative weight Kg/km | Electrical resistance at 20° C.
Maximum Ω/Km |
3 G |
1,5 | 1,5 | 0,7 | 12 | 146 | 13,30 |
2,5 | 2 | 0,7 | 13,50 | 191 | 7,98 | |
4 | 2,5 | 0,7 | 14,90 | 250 | 4,95 | |
6 | 3 | 0,7 | 16,20 | 320 | 3,30 | |
10 | 4 | 0,7 | 18,20 | 480 | 1,91 | |
16 | 5 | 0,7 | 20,60 | 705 | 1,21 | |
25 | 6,20 | 0,9 | 24,50 | 1060 | 0,78 | |
35 | 7,40 | 0,9 | 27,30 | 1400 | 0,554 | |
50 | 8,90 | 1 | 31,20 | 1910 | 0,386 | |
70 | 10,50 | 1,1 | 35,60 | 2590 | 0,272 | |
95 | 12,20 | 1,1 | 40 | 3320 | 0,206 | |
120 | 13,80 | 1,2 | 44,50 | 4130 | 0,161 | |
150 | 15,40 | 1,4 | 49,50 | 5200 | 0,129 | |
185 | 16,90 | 1,6 | 55,20 | 6650 | 0,106 | |
240 | 19,50 | 1,7 | 61,90 | 8700 | 0,0801 | |
300 | 22 | 1,8 | 68 | 10900 | 0,0641 |
QUADRIPOLAR | ||||||
Conductor
number n |
Nominal
section mmq |
Approximate
conductor diameter mm |
Average insulation
thickness mm |
Maximum external diameter
mm |
Indicative weight Kg/km | Electrial resistance at 20° C.
Maximum Ω/Km |
4 G |
1,5 | 1,5 | 0,7 | 13,40 | 168 | 13,30 |
2,5 | 2 | 0,7 | 14,60 | 220 | 7,98 | |
4 | 2,5 | 0,7 | 16 | 300 | 4,95 | |
6 | 3 | 0,7 | 17,50 | 390 | 3,30 | |
10 | 4 | 0,7 | 19,80 | 590 | 1,91 | |
16 | 5 | 0,7 | 22,40 | 865 | 1,21 | |
25 | 6,20 | 0,9 | 26,80 | 1310 | 0,78 |
PENTAPOLAR | ||||||
Conductor
number n |
Nominal
section mmq |
Approximate
conductor diameter mm |
Average insulation
thickness mm |
Maximum external diameter
mm |
Indicative weight Kg/km | Electrical resistance at 20° C.
Maximum Ω/Km |
5 G |
1,5 | 1,5 | 0,7 | 14,40 | 200 | 13,30 |
2,5 | 2 | 0,7 | 15,60 | 265 | 7,98 | |
4 | 2,5 | 0,7 | 17,30 | 355 | 4,95 | |
6 | 3 | 0,7 | 18,90 | 470 | 3,30 | |
10 | 4 | 0,7 | 21,50 | 710 | 1,91 | |
16 | 5 | 0,7 | 24,40 | 1050 | 1,21 | |
25 | 6,20 | 0,9 | 29,30 | 1590 | 0,78 | |
35 | 7,40 | 0,9 | 32,80 | 2110 | 0,554 | |
50 | 8,90 | 1 | 38,20 | 3210 | 0,386 |
MULTIPOLAR (numbered cores) | |||||||
Nominal
section mmq |
Approximate
conductor diameter mm |
Average insulation
thickness mm |
Maximum external diameter
mm |
Indicative weight Kg/km | Electrical resistance at 20° C.
Maximum Ω/Km |
||
7 | G | 1,5 | 1,5 | 0,7 | 15,40 | 305 | 13,30 |
7 | G | 2,5 | 2 | 0,7 | 16,80 | 420 | 7,98 |
10 | G | 1,5 | 1,5 | 0,7 | 18,70 | 395 | 13,40 |
10 | G | 2,5 | 2 | 0,7 | 20,60 | 525 | 8,06 |
12 | G | 1,5 | 1,5 | 0,7 | 19,30 | 440 | 13,40 |
12 | G | 2,5 | 2 | 0,7 | 21,30 | 595 | 8,06 |
16 | G | 1,5 | 1,5 | 0,7 | 21,10 | 545 | 13,40 |
16 | G | 2,5 | 2 | 0,7 | 23,30 | 750 | 8,06 |
19 | G | 1,5 | 1,5 | 0,7 | 22,10 | 620 | 13,40 |
19 | G | 2,5 | 2 | 0,7 | 24,50 | 845 | 8,06 |
24 | G | 1,5 | 1,5 | 0,7 | 25,40 | 765 | 13,50 |
24 | G | 2,5 | 2 | 0,7 | 28,30 | 1040 | 8,10 |