H07RN- F - 450/750 V EcaAccording to European Construction Products Regulation CPR (EU) n.305/11Reaction to fire REGULATION 305/2011/EU
  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Eca
  • Classification (CEI UNEL 35016): EN 13501-6:2014
  • Vertical flame spread: EN 60332-1-2
 Reference standardsCEI EN 60332-1CEI EN 50255-2-21CEI 20-19/4  HD 22.4 S4CEI 20-107/2-212006/95/CE2011/65/CE Cable descriptionHarmonised flame retardant rubber insulated polychloroprene (neoprene) sheathed cableswith high resistance to water, mineral oils, industrial greases and average mechanical stress,with good flexibility and good resistance to ozone and chemicals.ConductorFlexible bare copper CLASS 5InsulationSpecial elastomeric (rubber) EI4 qualityCore colour2x Brown / Light Blue3x Yellow-Green / Brown / Light Blue4x Yellow-Green / Black / Grey / Brown5x Yellow-Green / Black / Light Blue / Brown / GreySubsequent formations with numbered cores*Also available without G/VSheathPolychloroprene (Neoprene) with high mechanical propertiesSheath colourBlackLabelingWhite ink stamping on the conduit every 1 mTechnical specificationsRated voltage: Uo/U: 450/750 V c.a. - 0.6 /1 kV c.c.Maximum operating temperature: 60° CMinimum operating temperature: -40° C (in assenza di sollecitazioni meccaniche)Maximum short circuit temperature: 200° C Installation conditions Recommended minimum bending radius: 6 times the outside diameter of the cable for mobile laying3 times the outside diameter of the cable for fixed laying (if < or = 12mm)4 times the external diameter of the cable for fixed laying (if  >  12mm)Maximum recommended tensile stress:15 N/mm2 section for mobile laying50 N/mm2 of section for fixed layingPackaging
  • Hanks 100 metres
  • Wooden reel
 ApplicationsCables suitable for installation in dry, damp, wet and open areas, and in workshops with explosive atmospheres.For supplying and connecting mobile and lifting equipment and/or similar systems.Recommended for connections subject to medium mechanical stress: agricultural and industrial workshop equipment,heating plates, large kettles, portable lamps, power tools such as drills, motors or transportable machines on construction sites or in agricultural applications. They can also be used in temporary buildings or construction site huts.Use is permitted up to 1,000 V AC in the case of protected fixed installation in pipes.Mechanical protection is required when used in indirect underground installation (installation criteria for flexible cables). 
UNIPOLAR
Conductor numbernNominalSection Indicativeconductor diameter Average thickness Insulation Maximum outer diameter Indicative weight Kg/kmElectrical resistance at 20° C.Maximum 
         1 x1,51,50,87,15113,3
2,520,97,9677,98
42,519924,95
6319,81213,3
1041,211,91861,91
1651,213,42561,21
255,91,415,83680,780
357,31,417,94850,554
508,91,620,66680,386
7010,51,623,39050,272
9512,201,82611800,206
12013,801,828,614600,161
15015,40231,418100,129
18516,92,234,421650,106
24019,52,438,327500,0801 
 
BIPOLARI
ConductornumbernNominalsectionmmqApproximateconductor diametermmAverage insulation thicknessmmMaximum external diameter mmIndicative weight Kg/kmElectrical resistance at 20° C.MaximumΩ/Km
    2 x11,30,8109319,50
1,51,50,81111513,30
2,51,90,913,101657,98
42,5115,202254,95
63116,803003,30
1041,222,605501,91
1651,225,707401,21
256,21,430,7010600,78
 
TRIPOLARI
ConductornumbernNominalsectionmmqApproximateconductor diameter mmAverage insulationthicknessmmMaximum external diameter mmIndicative weight Kg/kmElectrical resistance at 20° C.MaximumΩ/Km
         3 G 11,300,810,7012019,5
1,51,500,81215013,30
2,520,913,502007,98
42,50114,902954,95
63116,203803,30
1041,218,206751,91
1651,220,609501,21
256,201,424,5013550,78
357,401,427,3017650,554
508,901,631,2024150,386
7010,501,635,6032300,272
9512,201,84042250,206
12013,801,844,5051900,161
15015,40249,5064150,129
18516,502,255,2077000,106
 
QUADRIPOLARI
ConductornumbernNominalsectionmmqApproximateconductor diametermmAverage insulationthicknessmmMaximum external diameter mmIndicative weight Kg/kmElectrical resistance at 20° C.MaximumΩ/Km
    4 G11,30,811,914519,5
1,51,50,813,117513,3
2,520,915,52557,98
42,5117,93554,95
631204853,30
1041,226,58451,91
1651,230,111851,21
256,201,436,617300,78 
 
PENTAPOLARI
ConductornumbernNominalsectionmmqApproximate conductor diametermmAverage insulation thicknessmmMaximum external diameter mmIndicative weight Kg/kmElectrical resistance at 20° C.MaximumΩ/Km
    5 G11,30,813,118019,5
1,51,50,814,422013,30
2,520,9173107,98
42,5119,94454,95
63122,26053,30
1041,229,110351,91
1651,233,314651,21
256,201,440,421450,78 
 
MULTIPOLARI (anime numerate)
NominalsectionmmqApproximateconductor sectionmmAverage insulationthicknessmmMaximum external diameter mmIndicative weight Kg/kmElectrical resistance at 20° C.MaximumΩ/Km
7G1,51,50,817,235513,3
7G2,520,9204957,98
12G1,51,50,822,450513,3
12G2,520,926,27107,98
19G1,51,50,826,372513,3
19G2,520,930,910357,98
24G1,51,50,830,791513,3
24G2,520,936,413257,98