FIRE RESISTANT
Reference standards :
UNI 9795 EN 50200/CEI/36-4-0 - CEI 20-29 EN 60228 CL.C - CEI EN 50363-0 - CEI EN 60332-1-2 - CEI EN 61034
20/37 IEC 61034-2 - CEI EN 50200 CEI 20/36-4-0 - CEI 20-105 UNI 9795
Cable description :
Cable for power supply, control and signalling to enable operation of safety systems in the event of fire
Conductor :
Red copper round flexible cord CLASS 5
Core isolation :
LSZH (elastomeric) compound quality G10
Shielding :
Cover 100% Aluminium/Polyester tape topped with flexible or rigid continuity conductor (red/tinned copper)
Sheath :
M1-quality LSZH compound (halogen free)
Sheath Color :
Red RAL 3000
Labeling :
Stamping on conduit every 1m.
Technical Specifications :
Fire resistance 30 min a 830 °C
Fire resistance 90 min a 830 °C
Fire resistance 120 min a 830 °C
Fire resistance 180 min a 750 °C
Operating voltage: 450/750 V
Maximum operating temperature: 90° C
Minimum operating temperature: -40° C
Short-circuit temperature: 350 °C
* Fire resistance grade to be specified
Installation conditions :
Recommended minimum bending radius: 8 times the cable diameter.
Applications :
Cable used for safety installations and circuits in hospitals, cinemas, fire pumps, public places where fire resistance of the cables used is required and the cable is able to withstand the high temperatures released in the event of fire.
For fixed indoor and outdoor installation. Can be installed on pipes, ducts, cable trays and similar systems.
Indirect underground laying allowed.
Packaging :
Hanks 100 metres – Wooden reel / Cardboard/plastic reels
Nominal
Section mmq |
Electrical resistance at 20° C.
<Maximum Ω/Km |
0,50 | 42 |
1 | 19 |
1,5 | 13,3 |
2,5 | 8 |